Make IPMI fan control temperature-aware without Docker
Manual fan mode pins the fans at a fixed duty and never ramps, so a sustained load had no cooling response until the BMC's own critical-temperature override stepped in. docker-idrac.sh solved that, but needs Docker, which is not installed on the host. ipmi-fancontrol-daemon polls the CPU sensors and switches between the fixed duty and the BMC's automatic curve around a threshold, which is what that container did. Measured on the host: 1440 RPM pinned versus roughly 4200 RPM on the automatic curve at the same 60C. - Hysteresis, default 5C, stops the fans oscillating at the boundary. - An unreadable temperature fails safe to automatic rather than staying pinned. - SIGTERM restores the automatic curve, with ExecStopPost as the backstop for an outright kill. Default to the local "open" interface. It needs no credentials and no network, which matters for the shutdown path, where lanplus to the iDRAC could fail once networking is down. ipmi-fancontrol-auto and -manual honour the same setting and stay available for ad-hoc use. Enable the third-party PCIe cooling response suppression that docker-idrac.sh was configured with, so the automatic curve is not held to a raised floor by the aftermarket NICs. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5
parent
af838987dd
commit
00384e7463
@@ -0,0 +1,122 @@
|
||||
#!/bin/bash
|
||||
# Temperature-aware IPMI fan control for Dell PowerEdge / iDRAC.
|
||||
#
|
||||
# Holds the fans at a fixed low duty while the CPUs are cool, and hands control
|
||||
# back to the BMC's automatic curve once they get hot, so there is still a
|
||||
# thermal response under load. This is the native equivalent of the
|
||||
# tigerblue77/dell_idrac_fan_controller container, without needing Docker.
|
||||
#
|
||||
# Run under ipmi-fancontrol.service. Configuration lives in
|
||||
# conf/ipmi-fancontrol.conf (see conf/ipmi-fancontrol.conf.example).
|
||||
|
||||
set -uo pipefail
|
||||
|
||||
SCRIPT_DIR=$(CDPATH= cd -- "$(dirname -- "${BASH_SOURCE[0]}")" && pwd)
|
||||
CONFIG=${IPMI_FANCONTROL_CONFIG:-$SCRIPT_DIR/conf/ipmi-fancontrol.conf}
|
||||
|
||||
if [[ ! -r "$CONFIG" ]]; then
|
||||
echo "Error: cannot read $CONFIG" >&2
|
||||
echo "Copy conf/ipmi-fancontrol.conf.example there and fill it in." >&2
|
||||
exit 1
|
||||
fi
|
||||
|
||||
# shellcheck source=/dev/null
|
||||
. "$CONFIG"
|
||||
|
||||
: "${IPMI_INTERFACE:=open}"
|
||||
: "${FAN_SPEED:=0x15}"
|
||||
: "${CPU_TEMP_THRESHOLD:=70}"
|
||||
: "${CPU_TEMP_HYSTERESIS:=5}"
|
||||
: "${CHECK_INTERVAL:=60}"
|
||||
: "${DISABLE_THIRD_PARTY_PCIE_COOLING_RESPONSE:=false}"
|
||||
|
||||
RESUME_AT=$((CPU_TEMP_THRESHOLD - CPU_TEMP_HYSTERESIS))
|
||||
|
||||
# Build the ipmitool invocation once. The local "open" interface needs no
|
||||
# credentials and no network, so it is the better choice for a polling loop;
|
||||
# lanplus stays available for reaching a BMC over the network.
|
||||
if [[ "$IPMI_INTERFACE" == "lanplus" ]]; then
|
||||
: "${IPMI_HOST:?not set in $CONFIG}"
|
||||
: "${IPMI_USER:?not set in $CONFIG}"
|
||||
: "${IPMI_PASSWORD:?not set in $CONFIG}"
|
||||
export IPMI_PASSWORD
|
||||
IPMITOOL=(ipmitool -I lanplus -H "$IPMI_HOST" -U "$IPMI_USER" -E)
|
||||
else
|
||||
IPMITOOL=(ipmitool -I open)
|
||||
fi
|
||||
|
||||
# stdout goes to the journal under systemd.
|
||||
log() { echo "$*"; }
|
||||
|
||||
set_manual() {
|
||||
"${IPMITOOL[@]}" raw 0x30 0x30 0x01 0x00 >/dev/null &&
|
||||
"${IPMITOOL[@]}" raw 0x30 0x30 0x02 0xff "$FAN_SPEED" >/dev/null
|
||||
}
|
||||
|
||||
set_auto() {
|
||||
"${IPMITOOL[@]}" raw 0x30 0x30 0x01 0x01 >/dev/null
|
||||
}
|
||||
|
||||
# Highest CPU temperature in degrees C, or empty if none could be read.
|
||||
# CPU sensors are entity 3.x; 7.x is the system board (inlet/exhaust).
|
||||
max_cpu_temp() {
|
||||
"${IPMITOOL[@]}" sdr type temperature 2>/dev/null | awk -F'|' '
|
||||
$4 ~ /^[[:space:]]*3\./ {
|
||||
if (match($5, /-?[0-9]+/)) {
|
||||
t = substr($5, RSTART, RLENGTH) + 0
|
||||
if (!seen || t > max) max = t
|
||||
seen = 1
|
||||
}
|
||||
}
|
||||
END { if (seen) print max }
|
||||
'
|
||||
}
|
||||
|
||||
MODE=""
|
||||
|
||||
cleanup() {
|
||||
log "Stopping: returning fan control to the BMC automatic curve."
|
||||
set_auto || log "Warning: failed to restore automatic fan control."
|
||||
exit 0
|
||||
}
|
||||
trap cleanup TERM INT
|
||||
|
||||
if [[ "$DISABLE_THIRD_PARTY_PCIE_COOLING_RESPONSE" == "true" ]]; then
|
||||
if "${IPMITOOL[@]}" raw 0x30 0xce 0x00 0x16 0x05 0x00 0x00 0x00 0x05 0x00 0x01 0x00 0x00 >/dev/null 2>&1; then
|
||||
log "Disabled the third-party PCIe card default cooling response."
|
||||
else
|
||||
log "Warning: could not disable the third-party PCIe cooling response."
|
||||
fi
|
||||
fi
|
||||
|
||||
log "Starting: fans held at $FAN_SPEED below ${CPU_TEMP_THRESHOLD}C, automatic at or above it, re-engaging at ${RESUME_AT}C. Polling every ${CHECK_INTERVAL}s over $IPMI_INTERFACE."
|
||||
|
||||
while true; do
|
||||
temp=$(max_cpu_temp)
|
||||
|
||||
if [[ -z "$temp" ]]; then
|
||||
# Fail safe: if the temperature cannot be read, let the BMC cool the box.
|
||||
if [[ "$MODE" != "auto" ]]; then
|
||||
log "Cannot read CPU temperature; failing safe to automatic fan control."
|
||||
set_auto && MODE="auto"
|
||||
fi
|
||||
elif (( temp >= CPU_TEMP_THRESHOLD )); then
|
||||
if [[ "$MODE" != "auto" ]]; then
|
||||
log "CPU at ${temp}C, at or above ${CPU_TEMP_THRESHOLD}C: handing control to the BMC automatic curve."
|
||||
set_auto && MODE="auto"
|
||||
fi
|
||||
elif [[ -z "$MODE" ]] || (( temp <= RESUME_AT )); then
|
||||
# The -z test makes the very first pass decide rather than drift, even
|
||||
# if we start up inside the hysteresis band.
|
||||
if [[ "$MODE" != "manual" ]]; then
|
||||
log "CPU at ${temp}C, at or below ${RESUME_AT}C: holding fans at $FAN_SPEED."
|
||||
set_manual && MODE="manual"
|
||||
fi
|
||||
fi
|
||||
# Inside the hysteresis band we deliberately keep whatever mode we are in.
|
||||
|
||||
# Backgrounded so that SIGTERM interrupts the wait instead of being deferred
|
||||
# until the sleep finishes.
|
||||
sleep "$CHECK_INTERVAL" &
|
||||
wait $!
|
||||
done
|
||||