Documents the target state for a host that owns a USB UPS and serves it to a
Synology, for hand-configuring a machine where running
setup-nut-synology.sh is not wanted. Verified byte-identical to what that
script generates, so the two cannot drift.

The [admin] password is the only real secret and ships as CHANGEME in both
files that must agree, upsd.users and the MONITOR line of upsmon.conf.

monuser/secret is committed literally. DSM hardcodes both and cannot be
configured otherwise, so they are published constants rather than
credentials, and the upsmon secondary role only permits reading status and
receiving shutdown notifications.

The example UPS serial is a placeholder rather than the real unit's.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-06 17:02:19 +00:00

42 lines
1.7 KiB
Markdown

# NUT configuration
Reference copies of `/etc/nut` for a host that owns a USB UPS and serves it to
other machines — in particular to a Synology, whose DSM client connects with
"UPS Type: Synology UPS Server".
`setup-nut-synology.sh` in the repo root generates all of these automatically by
detecting the UPS with `nut-scanner`. **Prefer running that.** These files are
here to document the target state and to hand-configure a host where you would
rather not run the script.
Install by copying each file to `/etc/nut/` without the `.example` suffix, then:
chown root:nut /etc/nut/*.conf /etc/nut/upsd.users
chmod 0640 /etc/nut/*.conf /etc/nut/upsd.users
systemctl enable --now nut-server nut-monitor
systemctl restart nut-driver@ups.service
## What DSM requires
DSM's client cannot be configured, so three things are fixed:
- the UPS must be named exactly `ups` — the `[ups]` section name in `ups.conf`
- it logs in as `monuser` with the password `secret`, both hardcoded
- `upsd` must listen on an address the Synology can reach
`monuser` / `secret` are therefore published constants, not credentials. The
`upsmon secondary` role only permits reading status and receiving shutdown
notifications; it cannot command the UPS.
## What you must change
The `[admin]` password is a real secret and appears in two files that must
agree: `upsd.users` and the `MONITOR` line of `upsmon.conf`. Both ship here as
`CHANGEME`. Generate one with:
openssl rand -base64 18 | tr -d '/+=' | cut -c1-20
`ups.conf` is pinned to a specific unit by `serial` and `product`. Re-run
`setup-nut-synology.sh` after swapping hardware, or drop those two lines to match
any UPS of the same model.