Documents the target state for a host that owns a USB UPS and serves it to a Synology, for hand-configuring a machine where running setup-nut-synology.sh is not wanted. Verified byte-identical to what that script generates, so the two cannot drift. The [admin] password is the only real secret and ships as CHANGEME in both files that must agree, upsd.users and the MONITOR line of upsmon.conf. monuser/secret is committed literally. DSM hardcodes both and cannot be configured otherwise, so they are published constants rather than credentials, and the upsmon secondary role only permits reading status and receiving shutdown notifications. The example UPS serial is a placeholder rather than the real unit's. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
42 lines
1.7 KiB
Markdown
42 lines
1.7 KiB
Markdown
# NUT configuration
|
|
|
|
Reference copies of `/etc/nut` for a host that owns a USB UPS and serves it to
|
|
other machines — in particular to a Synology, whose DSM client connects with
|
|
"UPS Type: Synology UPS Server".
|
|
|
|
`setup-nut-synology.sh` in the repo root generates all of these automatically by
|
|
detecting the UPS with `nut-scanner`. **Prefer running that.** These files are
|
|
here to document the target state and to hand-configure a host where you would
|
|
rather not run the script.
|
|
|
|
Install by copying each file to `/etc/nut/` without the `.example` suffix, then:
|
|
|
|
chown root:nut /etc/nut/*.conf /etc/nut/upsd.users
|
|
chmod 0640 /etc/nut/*.conf /etc/nut/upsd.users
|
|
systemctl enable --now nut-server nut-monitor
|
|
systemctl restart nut-driver@ups.service
|
|
|
|
## What DSM requires
|
|
|
|
DSM's client cannot be configured, so three things are fixed:
|
|
|
|
- the UPS must be named exactly `ups` — the `[ups]` section name in `ups.conf`
|
|
- it logs in as `monuser` with the password `secret`, both hardcoded
|
|
- `upsd` must listen on an address the Synology can reach
|
|
|
|
`monuser` / `secret` are therefore published constants, not credentials. The
|
|
`upsmon secondary` role only permits reading status and receiving shutdown
|
|
notifications; it cannot command the UPS.
|
|
|
|
## What you must change
|
|
|
|
The `[admin]` password is a real secret and appears in two files that must
|
|
agree: `upsd.users` and the `MONITOR` line of `upsmon.conf`. Both ship here as
|
|
`CHANGEME`. Generate one with:
|
|
|
|
openssl rand -base64 18 | tr -d '/+=' | cut -c1-20
|
|
|
|
`ups.conf` is pinned to a specific unit by `serial` and `product`. Re-run
|
|
`setup-nut-synology.sh` after swapping hardware, or drop those two lines to match
|
|
any UPS of the same model.
|